• Calibration
General
The PTX800A analogue outputs and Inputs are calibrated for a specific
range and type. If you have changed the range or type you must follow
the appropriate procedure.
Allow the instrument 15 minutes of powered operation (to reach a
stable temperature) before calibration.
Note: the procedures below shows calibration for the commonly
u
s
ed 4-20 mA format. If you have chosen another format, the unit will
prompt you with the high and low values you have selected.
Equipment requirements
• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)
• Suitable current/voltage source (accurate to 0.05 mV and ±0.1 μA)
Output Calibration
Terminal Connections for output calibration are:
Calibration Stage Signal type Terminal
Analogue Current Output
mA output + 3
mA output – 4
Analogue Voltage Output
V output + 3
V output – 4