UTC/AR 61001024/00/02.08
Bedienungsanleitung
Signalwandler
mit Hilfsspannungsversorgung
und Grenzwertüberwachung
3
Operating instructions
Signal converter with auxiliary
voltage supply and threshold
monitoring
16
Vista de pagina 0
1 2 3 4 5 6 ... 27 28

Indice de contenidos

Pagina 1 - Operating instructions

deenUTC/AR 61001024/00/02.08BedienungsanleitungSignalwandler mit Hilfsspannungsversorgung und Grenzwertüberwachung 3Operating instructionsSignal c

Pagina 2

10• KalibrierungAllgemeinDas UTC/AR ist werksseitig auf einen bestimmten Ausgangsbereich bzw. ein bestimmtes Ausgangssignal kalibriert. Warten Sie wäh

Pagina 3

11Vorgehensweise bei der EingangskalibrierungAnzeige Aktion/Beschreibung ENTïAktivieren Sie den Konfigurationsmodus des Gerätes, und scrollen Sie durch

Pagina 4 - Betrieb

12Vorgehensweise bei der AusgangskalibrierungAnzeige Aktion/Beschreibungì ÅENTAktivieren Sie den Konfigurationsmodus des Gerätes, und scrollen Sie durc

Pagina 5 - Å und ì

13• KonfigurationssequenzEinstellung Anzeige BeschreibungÅ ìENTS/W Versionv1.01Softwareversion 1.01 (Hinweis: Diese Informationen beziehen sich nur auf

Pagina 6

14Alarmkanal 1Coil energisationA1nE A1ndNormalerweise erregtNormalerweise nicht erregtToggle AcceptAlarm typeA1=LA1=HA1=0Typ ‘niedrig’ (unterhalb Soll

Pagina 7

15Analoge AusgängeHinweis: Wenn Sie den Ausgangsbereich oder -typ ändern, müssen Sie eine Kalibrierung der Ausgänge durchführen.AnalogeOutput typeOP=I

Pagina 8 - Mi llivoltsignale

16en UTC/ARContentsOperation 17Installation 20Setup 21Calibration 22Setup Sequence 24

Pagina 9 - • Konfiguration

17en UTC/AR• OperationGeneralThe UTC/AR measures temperatures using type J, K, N, T, E, B, S or R thermocouples and produces an industry standard, ana

Pagina 10 - • Kalibrierung

18Sensor diagnosticsYou can order either upscale or downscale burnout protection and use alarm channel one as a sensor burnout alarm if required.The d

Pagina 11 - Å oder ì

19InputThermocouple Input +Thermocouple Input –Power supplyLive (+)Neutral (–)109Alarm outputsCommonChannel 2Channel 17814Link to enable full setup(no

Pagina 13 - • Konfigurationssequenz

20• InstallationGeneralThese units must only be installed by qualified staff in accordance with the information given in this manual and all relevant

Pagina 14

21-+Millivolt source2 3Shielded copper wireUTC/ARMillivol t signal s• SetupChanging the setupFor setup mode, connect the security link and press the Å

Pagina 15

22• CalibrationGeneralThe UTC/AR is factory calibrated to a specific output range and format. During calibration allow a few seconds for signals to st

Pagina 16

23Terminal connections for output calibrationCalibration Stage Signal type TerminalAnalogue Current OutputmA output + 14mA output − 15Analogue Voltage

Pagina 17 - Operation

24• Setup SequenceSetting Display DescriptionÅ ìENTS/W Versionv1.01S/W Version 1.01 (Note: this information only applies to versions 1.00 to 1.09)Dis

Pagina 18 - Å and ì keys simultaneously

25Alarm channel oneCoil energisationA1nE A1ndNormally energisedNormally de-energisedToggle AcceptAlarm typeA1=LA1=HA1=0Low type (active below setpoint

Pagina 19 - 1 2 3 4 5 6 7 8

26Analogue outputsNote: if you change the output range or type, you will be required to calibrate the outputs.AnalogueOutput typeOP=IOP=ECurrent based

Pagina 21 - Å and ì

Weidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldTel. +49 5231 14-0Fax +49 5231 14-20 83info@weidmuell

Pagina 22 - • Calibration

3de UTC/ARInhaltsverzeichnisBetrieb 4Installation 7Konfiguration 9Kalibrierung 10Konfigurationssequenz 13

Pagina 23 - Output calibration procedure

4de UTC/AR• BetriebAllgemeinDer temperaturmesswandler UTC/AR ist für den Anschluss von Thermoelementen des Typs J, K, N, T, E, B, S oder R geeignet. E

Pagina 24 - • Setup Sequence

5SensordiagnoseErhältlich ist wahlweise eine Upscale- oder Downscale-Drahtbruchtrennung. Darüber hinaus können Sie bei Bedarf Alarmkanal 1 als Drahtbr

Pagina 25 - Setup Sequence (continued)

6EingangThermoelementeingang +Thermoelementeingang – StromversorgungPhase (+)Neutral (–)109AlarmausgängeWurzelkontaktSchließerkanal 2Schließerkanal 17

Pagina 26

7Alarmsollwerte anpassenEinen Sollwert können Sie ändern, indem Sie die diesem Kanal zugewiesene Taste (ï für Alarm 1 oder ENT für Alarm 2) gedrückt h

Pagina 27

8-+Millivoltquelle2 3Geschirmte KupferleitungUTC/ARMi llivoltsignaleAnforderungen an die StromversorgungBevor Sie das Gerät an die Stromversorgung ans

Pagina 28

9• KonfigurationKonfiguration ändernZum Aufrufen des Konfigurationsmodus schließen Sie die Sicherheitsverbindung an, und drücken Sie die Tasten Å und ì