Terminal connections for output calibration
Calibration Stage Signal type Terminal
Analogue Current Output
mA output + 14
mA output − 15
Analogue Voltage Output
V output + 14
V output − 16
Output calibration procedure
When the
display shows
Action/Description
ì Å
ENT
Put the instrument in setup mode and scroll through the main menu
COPn
Press Å or ì
COPy
Calibrate Outputs? Toggle Start
OPL=
Connect the multimeter to measure the output (as a current or voltage as
chosen during setup)
Next
1.00
The output current should be at the required zero
value, e.g., 1.00 V for 1-5 V output.
(Use the keypad to adjust the value as required)
Increase Decrease Accept
5.00
The output current should be at the required full
scale value, e.g., 5.00 V for 1-5 V output.
(Use the keypad to adjust the value as required)
Increase Decrease Accept
Save
Instrument will save values and return to normal operation (using the new values).
Note: Do not remove the power while the save message is on display.