UHZ/AR 61001022/00/02.08
Bedienungsanleitung
Signalwandler
mit Hilfsspannungsversorgung
und Grenzwertüberwachung 3
Operating instructions
Signal converter with auxiliary
voltage supply and threshold
monitoring 14
Vista de pagina 0
1 2 3 4 5 6 ... 23 24

Indice de contenidos

Pagina 1 - Operating instructions

deenUHZ/AR 61001022/00/02.08BedienungsanleitungSignalwandler mit Hilfsspannungsversorgung und Grenzwertüberwachung 3Operating instructionsSignal con

Pagina 2

10Klemme Signal1 12 V DC (Ausgang)Eingangssignal/-sensor2 Pull Up/Down3 0V4 Signal +5 Signal −6 Hochspannungssignal +7Verbindung für die Gerätekonfigu

Pagina 3

11Anforderungen an die StromversorgungBevor Sie das Gerät an die Stromversorgung anschließen, überprüfen Sie anhand der Typenbezeichnung, ob diese den

Pagina 4 - • Betrieb

12Vorgehensweise bei der AusgangskalibrierungAnzeige Aktion/Beschreibungì ÅENTWarten Sie, bis das Gerät 15 Minuten in Betrieb war (und damit eine stab

Pagina 5 - Å und ì

13NAMUR-Sensor–UHZ/AR3+ 1 2 4NAMUR-SensorenNPN-Typ-3-Draht-Sensor(O/C-Ausgänge)Sig–UHZ/AR2+ 5Spannung (+ve)SignalSpannung (–ve)413-Drahtsensoren mit N

Pagina 6

14en UHZ/ARContentsOperation 15Setup Sequence 18Installation 20Calibration 21

Pagina 7 - • Konfigurationssequenz

15en UHZ/AR• OperationGeneralThe UHZ/AR is an auxiliary powered, signal converter for frequency based signals. It has two alarm channels and a digital

Pagina 8

16Reviewing the setupFor review mode, press the Å and ì keys simultaneously. Press the Å and ì keys to move through the setup sequence (see table). Gr

Pagina 9

17Adjusting the alarm setpointsTo change a setpoint, hold down the key for that channel ( ï for Alarm 1 or ENT for Alarm 2). You will then be able to

Pagina 10 - Anschlüsse (Fortsetzung)

18• Setup SequenceSetting Display DescriptionÅ ì ïENTS/W Version1.31S/W Version 1.31 (Note: this information only applies to versions 1.30 to 1.39)Di

Pagina 11 - • Kalibrierung

19Alarm typeA1=LA1=HLow type (active below setpoint)High type (active above setpoint)Toggle AcceptSetpoint valueSP1=50.0Setpoint valuee.g., 50.00 %- D

Pagina 13 - Eingangstypen

20• InstallationThese units must only be installed by qualified staff in accordance with the information given in this manual and all relevant nationa

Pagina 14

21Power Supply RequirementsCheck the power supply against the model number before applying power to the instrument. Micromann modules must be used wit

Pagina 15 - • Operation

22Equipment requirements• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)Output calibration procedureWhen thedisplay showsAction/Desc

Pagina 16 - Å and ì

23NAMURsensor–UHZ/AR3+ 1 2 4NAMUR sensors.NPN type3-wire sensor(O/C outputs)Sig–UHZ/AR2+ 5Power (+ve)SignalPower (–ve)413-wire sensors with NPN open c

Pagina 17

Weidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldTel. +49 5231 14-0Fax +49 5231 14-20 83info@weidmuell

Pagina 18 - • Setup Sequence

3de UHZ/ARInhaltsverzeichnisBetrieb 4Konfigurationssequenz 7Installation 9Kalibrierung 11

Pagina 19 - Setup Sequence (continued)

4de UHZ/AR• BetriebAllgemeinDas UHZ/AR ist ein Frequenzanalogwandler mit Hilfsstromversorgung für frequenzbasierte Signale. Es ist zusätzlich mit zwei

Pagina 20 - • Installation

5Konfiguration prüfenZum Aufrufen des Prüfmodus drücken Sie die Tasten Å und ì gleichzeitig. Durch Drücken der Taste Å und ì (siehe Tabelle) können Sie

Pagina 21 - • Calibration

6Alarmsollwerte anzeigenEinen Sollwert können Sie überprüfen, indem Sie die diesem Kanal zugewiesene Taste (ï für Alarm 1 oder ENT für Alarm 2) drücke

Pagina 22

7• KonfigurationssequenzEinstellung Anzeige BeschreibungÅ ì ïENTS/W Version1.31Softwareversion 1.31 (Hinweis: Diese Informationen beziehen sich nur auf

Pagina 23 - Input Types

8Alarmkanal 1Coil energisationA1nE A1ndNormalerweise erregtNormalerweise nicht erregtToggle AcceptAlarm typeA1=LA1=HTyp ‘niedrig’ (unterhalb Sollwert

Pagina 24

9• InstallationDie Installation dieser Geräte darf nur von speziell ausgebildetem Fachpersonal, unter Beachtung der in dieser Dokumentation enthaltene