Input signal type and range
You can not change the input type during set-up mode. The input is
either current or voltage according to the components used when the
unit was built.
The input range is determined by the values supplied during
calibration. So, if you change the range displayed in setup, you will
have to calibrate the inputs.
D
a
mping Factor
The PTX800A uses digital filtering to smooth the input signal. The
damping factor sets the amount of filtering from minimum damping
(factor of one) to the maximum (factor of ninety nine).
Tr
ansfer Function
To use the PTX800A with square law rate measuring devices, like
differential pressure cells, set the transfer function to square law.
Otherwise use a linear setting. For more complex relationships
between rate and signal level you can use a CLC/AR to linearise your
input signal.
Lo
w cut-out rate
To prevent accumulated errors at low input levels, you can set a low
cut-out rate. When the input is below this value the total does not
increase.
To
tal decimal point
The total decimal point position sets the number of decimal places for
the total display. Totals are displayed using the full eight digits.
Ra
te decimal point
Sets the number of decimal places for the rate display. Rates are
displayed as five digit numbers.