• Modifications
Analogue output type
The analogue output type (current/voltage) is set by internal push fit
jumper. To change the output type:
Change the output type push fit jumper:
1. Gently remove the backplate (it is held in place by four lugs).
2. S
lid
e the electronics from the housing.
3. Change the jumper location to the required setting (see diagram
above).
4. Loo
k inside the housing and note that there are connectors that
mate with the display board.
5. Sl
ide the electronics gently back into the case. Carefully moving the
board until the keypad connectors engage with the display board.
6. Rep
lace the backplate.
Change the output type in the software:
1. Power up the instrument and start the setup routine.
2. Whi
le the software version number is flashing, remove the security
link and press PGM.
3. The d
isplay will show Aout_=_y. Press PGM.
4. The d
isplay will show Aout=volt or Aout=_cur. Select using up
or down key.
5. Replace the security link and press PGM.
Change the output range settings:
6.
Scr
oll through the setup and change the output type and range
settings - you will be required to calibrate the outputs.
Calibrate the output:
7. C
ali
brate the outputs to the new output range and type.