23
Procedure
Note: The procedure below shows calibration for the commonly used
4-
20 mA format. If you have set the outputs to any other format, the
unit will prompt you with the output high and low values you have
chosen. If you are calibrating the unit for a voltage output you must
measure the output voltage.
When the
display shows
Action/Description
Put the instrument in setup mode and scroll through the main menu
COPn
Press ì or Å
COPy
Press ENT to select output calibration
OPL=
Connect the multimeter to measure the output signal, then press ENT
4.00
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press ENT
OPH=
Press ENT
20.00
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press ENT
Save
Continue with the setup sequence.
Note: Do not remove the power while the save message is on display.
Output type selection
If the output type needs to be changed, remove the back plate by
gently prising apart the four clips that hold it in place, place the link
(on the analogue output board) as apropriate and reassemble.
Then change the output type in the software:
1. Start the set-up sequence and, while the software version number is
flashing, remove the security link and press ENT.
2. The display will show OP=C (for current inputs) or
OP=v (for voltage inputs). Select the correct value, replace the security
link and press ENT.
3. The instrument is now in set-up mode. Scroll through and complete
the output calibration procedure as described above.