Alarm channel four settings*
Coil energisation
A4nE
A4nd
Normally energised
Normally de-energised
Toggle Accept
Alarm type
A4=L
A4=H
A4=G
A4=S
Low type (active below setpoint)
High type (active above setpoint)
Group alarm
Siren alarm (manual reset mode only)
Toggle Accept
Note: for group or siren alarms, the setpoint, deadband and timer settings are skipped
Setpoint value
SP1=
50.00
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
10.00
Deadband value
e.g., 10 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
0
Timer delay (set to 0 s to disable)
e.g., no delay
-
Dec
-
Inc
Next
Accept
C
alibration options
Calibrate
Output?
COPy
COPn
Skip output calibration
Calibrate outputs
Toggle Accept
Save values
SAVE
Instrument is saving the changes to the setup and returning to
normal operation
• Output calibration
General
The PMX400HZX analogue outputs are calibrated for a specific output
range and type. If you have changed the output range or type you
must follow the procedure given below.
E
quipment requirements
• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)
Terminal Connections for output calibration
Calibration Stage Signal type Terminal
Analogue Current Output
mA output + 3
mA output 4
Analogue Voltage Output
V output + 3
V output 4
Setup Sequence (continued)