Procedure
Note: Allow 15 mins of powered operation before calibration.
Analogue Output Calibration
When the
display shows
Action/Description
Put the instrument in setup mode and scroll through the main menu
COPn
Press ì or Å
COPy
Press ENT to select output calibration
OPlO
Connect the multimeter to measure the output signal, then press ENT
Adjust the output (using the ì or Å keys) until the output is at the output range
minimum.
When you are happy that the output is correct, press ENT
OPHI
Press ENT
Measure the output signal
Adjust the output (using the ì or Å keys) until the output is at the output range
maximum
When you are happy that the output is correct, press ENT
Save
Continue with the setup sequence.
Note: Do not remove the power while the save message is on display.
• Digital Input Type Selection
General
The AMS400A Digital Input Type can be selected using two push-fit
j
umpers on J3 and J4 on the main board.
• For volt free contacts use positions a-b and d-e.
• For Voltage Inputs use positions b-c and e-f.
The Digital Inputs are connected by these jumpers to the Analogue
input circuit. You can remove the jumpers to isolate the two circuits
for voltage type inputs. If you need higher isolation, remove linking
r
esistors R16 and R23 - marked with single black line (DC powered
units only).