29
Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
t
ighten to 4.5 lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multistranded wires (do not solder).
Terminal Signal
1 Neutral / −
Power supply
2 Live / +
3 Signal +
Analogue output
4 Signal −
5 0V
Status Outputs6 AUTO/MAN
7 Handover Status
8 Common
Digital Input9 Increment
10 Decrement
11 Signal +
Analogue Input
12 Signal −
13 Normally Closed
Increment
Relay Output
14 Common
15 Normally Open
16 Normally Closed
Decrement
Relay Output
17 Common
18 Normally Open