Wireless I/O Expansion I/O Units—Introduction 900 MHz
10
WI-I/O–EX-1-S Expansion I/O Units (Serial I/O)
Typical Applications
Expansion I/O for WI-I/O 9 wireless units
- up to 31 x WI-I/O-EX-1-S units can be connected to each wireless unit via RS485 (up to 2 km long).
Serial I/O multiplexer
- transfer I/O via RS485— up to 32 units per multi-drop link.
Expansion I/O for Modbus devices
- up to 31 x WI-I/O-EX-1-S units can be connected to each Modbus master via RS485 (up to 2 km long).
Features
Multi I/O channels— monitoring and control functions
Connected via RS485 multi-drop
Selectable communications via Modbus protocol (both RTU and ASCII formats)
Sensor signals connected at one module (input signals) are transmitted to another module where the signals are re-created
as output signals, or passed via serial to a host device such as a PLC or SCADA system
Connect to WI-I/O 9 wireless I/O units for up to 31 serial addresses per wireless unit
Connect WI-I/O-EX-1-S units together to form a serial multi-drop I/O system - up to 32 serial addresses per multi-drop link—
no Master device is required to control communications
Connect up to 99 x WI-I/O-EX-1-S units as multi-drop Modbus I/O
(RS485 extenders/isolators required for more than 31 units per single multi-drop length)
RS485 multi-drop up to 2 km (1 mile) depending on installation environment
Three I/O versions available
67200005035 67200005036 67200005037
WI-I/O-EX-1-S -11 -12 -13
Digital inputs up to 16 up to 8 up to 8
Voltage-free contacts
Digital outputs up to 16 up to 8 up to 8
FET
Analog inputs 0 4 “floating”/ 8 commoned 0
0-20mA / 0-10V
Analog outputs 0 0 8 sink / source
0-20mA / 0-10V
Pulse inputs 4 0 0
1KHz
Pulse outputs 8 8 8
15Hz 15Hz 15Hz
Note: Digital inputs and outputs are combined channels. When a channel is used as an output, it is not available as an input. Pulse and
digital I/O are same connection.
Peer-to-peer communications; Exception reporting; Reliable self-checking messages;
Any input on any unit can be linked to any output on any unit. Inputs can be linked to multiple outputs;
Serial communications 9.6Kb/s
Alternate Modbus RTU or Modbus ASCII slave protocol, serial communications configurable up to 115.2Kb/s,
7 or 8 data bit format
External I/O plus internally calculated values - analog setpoint status, pulse rate and pulse total,
power supply voltage, power supply alarm
Setpoint status generated by comparing analog inputs to high and low setpoints
Analog inputs selectable as “floating” dual-terminal inputs or commoned single-terminal inputs;
Configurable current (0-10/0-20/4-20mA) or voltage (0-5/0-10/1-5V).
Analog outputs selectable as single-terminal source or sink outputs. Configurable current (0-10/0-20/4-20mA)
or voltage (0-5/0-10/1-5V). Configurable scaling, zero and span parameters.
Pulse inputs generate separate pulse count value and a pulse rate value. Pulse rates are treated as internal analog registers
with a configurable maximum value.
Multiple communication-failure diagnostics with output status. Fail-to-transmit alarm and fail-to-receive alarm status.
Class 1 Div 2 hazardous areas approval
Input measurement display and output “forcing” diagnostics.
Communication logging diagnostics.
Easy-to-use E-Series Windows configuration.