4. Mounting
Die The analogue signal isolators are mounted on standard TS 35 rails.
5. Electrical connection
Warning! For applications with high isolation voltages, take measures to
prevent accidental contact and make sure that there is suffi-
cient distance or insulation between adjacent devices!
5.1 Power supply
approx. 1 W
18…30 Vdc
Voltage supply via cross-connections. Operating carrying capacity of
cross-connection 2 A (see Cat. No. point 7)
Terminal assignments
1 +15 V power supply for sensor
2 Input PNP
3 Input NPN / Namur
4 Input GND
5 Output (0...10 V; 0/4...20 mA)
6 Output GND
7 Supply voltage + 24 Vdc (cross-connected)
8 Power supply GND (cross-connected)
Wire cross-section max. 2.5 mm
2
Multi-wire conncection max. 1 mm
2
(two wires with same cross-section)
6
7
1
2
8
3
4
5