WAVESERIES PT 100/2
and PT 100/3 Signal Conditioners
for Current Output
Type Cat. No.
Screw-type connection
WTS4 PT100/2 Select C 8432210000
WTS4 PT100/3 Select C 8432150000
Tension clamp connection
WTZ4 PT100/2 Select C 8432220000
WTZ4 PT100/3 Select C 8432160000
Read these instructions before using the product
and retain for future information.
Vista de pagina 0
1 2 3 4 5 6 ... 13 14

Indice de contenidos

Pagina 1

15WAVESERIES PT 100/2and PT 100/3 Signal Conditionersfor Current OutputType Cat. No.Screw-type connectionWTS4 PT100/2 Select C 8432210000WTS4 PT100/3

Pagina 2

24ExampleInput range: -50 ... +150 °CMinimum input temperature: = -50 °CChoose next lower or equal value according to table for ϑmin.Table value -60 °

Pagina 3

255 Electrical connection2-wire technology 3-wire technology(s. Fig. 6) (s. Fig. 7)6 Dimensions(s. Fig. 8)7 Notes on CE labelling of WAVESERIES module

Pagina 4

268 Technical dataInputSensor types PT 100/2 Select C, PT 100/3 SelectC according to DIN IEC 751Input current 1.35 mA ... 1.45 mA ... 1.60 mAConductor

Pagina 5

27Connection dataConnection BLZ/SLInsulating stripping length 8 ± 0.5 mmSolid core 0.5 ... 2.5 mm2Flexible core 0.5 ... 2.5 mm2With ferrules 0.5 ... 1

Pagina 6

289 AccessoriesCross-connection ZQV 2,5N/2 black 1718080000Cross-connection ZQV 2,5N/2 red 1717900000Cross-connection ZQV 2,5N/2 blue 1717990000Cross-

Pagina 7

161 General instructionsThe WAVESERIES signal conditioner PT 100 should only beinstalled by qualified staff. The signal conditioner PT 100 shouldonly

Pagina 8

173.1 Mounting onto TS 35 DIN rails(s. Fig. 1)3.2 Pluggable electronic components for range alteration(depending on model)(s. Fig. 2)1. Remove connect

Pagina 9

183.3 Setting the potentiometer (depending on model)(s. Fig. 3)The module has been exactly calibrated by the manufacturer.Should nevertheless a follow

Pagina 10

194 CalibrationWarning!! The power supply must be disconnected, beforechanging the signal conditioner settings using theDIP switches.Failure to observ

Pagina 11

202. Professionally install module.3. Add 1 % of the temperature span to the selected "minimum"temperature and set this value on a PT 100 si

Pagina 12

214.3 Calibration with an signal output from 4 ... 20 mA1. Set the required temperature range on the printed circuitboard using the DIP switch, see ta

Pagina 13

224.4 Setting the DIP switchesWarning!! The signal conditioner PT 100 must be protectedagainst a direct electrostatic discharge when settingthe DIP sw

Pagina 14

23DIP switchesSpan 4 5 640 ... 50 °C ON ON ON50 ... 75 °C ON ON OFF75 ... 110 °C ON OFF ON110 ... 165 °C ON OFF OFF165 ... 245 °C OFF ON ON245 ... 360