Output Calibration
1. Measure the output current.
2. Select ‘Calibrate output’ from the ‘Device’ menu.
3. E
nter the calibration password.
4. The 4 mA adjustment window will open. Adjust the output to
4.00 mA using the buttons shown.
Note: you can use PgUp and PgDn controls on the keyboard for
fine adjustment and <CNTRL> + PgUp and <CNTRL> + PgDn for
coarse adjustment.
5
. Press Next when the output has settled at 4.00 mA.
6. Repeat the procedure for the 20.00 mA adjustment.
7
. Press OK to save the changes to the instrument.
This completes the output calibration.