
30
Communications Setup
Allows you to configure the RS422/RS485 outputs.
Display Setup
Sets up display scrolling options.
User Definitions
The ‘User’ Definition’ menu allows you to set one ‘User Defined’
linearisation curve for use by any of the inputs. It also allows you to set
up character sequences for four ‘User Defined’ Engineering Units.
• Calibration Mode
General
The AI8 is factory calibrated. Once calibrated it will operate with
any input or output format without calibration. You should not have to
calibrate the unit before installation.
Allow the instrument 15 minutes of powered operation (to reach a
stable temperature) before calibration.
During calibration allow a few seconds for signals to stabilise before
accepting the value.
ENT
EXIT
EXIT
EXIT
ENT
Calibration Mode
Prev Next
To Run
Mode
Calibrate P.I.N
101
Defau t P N = 101
Lower PIN
Calibrate Output
Prev Next
ENT
Calibrate Input
Prev Next
Select which input to calibrate
Previous Output Channel
ENT
Calibrate Output
Next Output Channel
EXIT
Exit
Calibrate
Output 1
Raise PIN
ENT
Input calibration Procedure (see below)
EXITMENU
ENT
Invalid PIN
Menu->Retry
Comentarios a estos manuales