Power Supply Requirements
Check the power supply against the model number before applying
power to the instrument. Micromann modules must be used with a
suitable mains Power Supply, ratings are as follows:
Voltage Range Nominal Voltage Power Frequency
100–132 V AC 110 V AC 6 VA 47-63 Hz
200264 V AC 240 V AC 6 VA 47-63 Hz
12–50 V DC* 24 V DC 6 W (at 24 V DC) -
*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.
Connections
Terminal Signal
1 Not used
Input signals
2 A
3 B
4 B
sense
5 Not used
6 Not used
7
Link to change the set-up Security Link
8
9 Neutral (−)
Power supply
10 Live (+)
11 Normally Closed
Alarm Channel One12 Common
13 Normally Open
14 Normally Closed
Alarm Channel Two15 Common
16 Normally Open
Case Earthing is via a stud on lower side of case