Weidmuller DC/DC CCC HF - with 3 way separation Manual de usuario Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 5
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
14 15
Temperature coefficient 250 ppm/K from measuring
range
Step response time 40 µs (typ. 30 µs)
Cut-off frequency (-3 dB) 15 Hz (typ. 20 kHz)
Coordination of Insulation according to EN 50178, 04.98
Rated Voltage 300 V
Rated surge Voltage 4 kV
Overvoltage category III
Contamination class 2
Clearance and
creepage distances 3 mm
Coupling capacity
Input/output/supply 1 nF
Isolation voltage
Voltage endurance
Input/output/to mounting rail 4 kV
eff
/1 min
Connection data
Connection BLZ/SL
Insulating stripping length 8 ± 0.5 mm
Solid core 0.5 ... 2.5 mm
2
Flexible core 0.5 ... 2.5 mm
2
With ferrules 0.5 ... 1.5 mm
2
EMC specification according to EN 55011,
class B, group 1
according to EN 50081-1
according to EN 50082-2
General
Voltage supply 24 Vdc ± 25 % (18 ... 30 Vdc)
Power consumption < 1.5 W at I
out
= 20 mA (at output
0 ... 20 mA, 4 ... 20 mA)
< 1.3 W at I
out
= 5 mA
(at output 0 ... 10 V)
Cross-connection, upper 24 V, max. 2 A
Cross-connection, lower 0 V, max. 2 A
Operating temperature 0 ... +55 °C
Storage temperature -20 ... +85 °C
Approvals CE, CSA, UL
Vista de pagina 3
1 2 3 4 5

Comentarios a estos manuales

Sin comentarios