7 Technical data
Input
Input signal 0 ... 20 mA or 0 ... 10 V
Input voltage, max. 15 V (0 ... 10 V)
Input current, max. 25 mA (0 ... 20 mA)
Input resistance 50 Ω (0 ... 20 mA)
500 kΩ (0 ... 10 V)
Output
Output signal 0 ... 20 mA or 4 ... 20 mA
or 0 ... 10 V
Load resistance ≤ 500 Ω (0 ... 20 mA, 4 ... 20 mA)
≥ 1 kΩ (0 ... 10 V)
Accuracy at T
u
= 23 °C ± 0.2 % from end value
Temperature coefficient ≤ 250 ppm/K from measured
value