Weidmuller WI-I/O-9-U2: Wireless Mesh I/O & Gateway User Manual de usuario Pagina 116

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 126
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 115
115
I/O store for a WI-I/O-EX-1-S-12 Expansion I/O module
0001 + Offset
0008 + Offset
DIO Outputs 1 - 8
10001 + Offset
10008 + Offset
DIO Inputs 1 - 8
10019 + Offset
Modbus Error indication for WI-I/O-EX-1-S module
10020 + Offset
Detected indication for this WI-I/O-EX-1-S module
30001 + Offset
30008 + Offset
Inputs AIN 1 AIN8
30017 + Offset
Modbus Error Counter for this WI-I/O-EX-1-S module
30018 + Offset
Modbus Last Error Code for this WI-I/O-EX-1-S module. (Section 5.1.3
30019 + Offset
Modbus Lost Link Counter for this WI-I/O-EX-1-S module
30020 + Offset
Module type (0x0201) = 513. / Error Status
40009 + Offset
40016 + Offset
Pulsed Output target 1 8 (1 register per output)
I/O store for a WI-I/O-EX-1-S-13 Expansion I/O module
0001 + Offset
0008 + Offset
DIO Outputs 1 - 8
10001 + Offset
10008 + Offset
DIO Inputs 1 - 8
10019 + Offset
Modbus Error indication for WI-I/O-EX-1-S module
10020 + Offset
Detected indication for this WI-I/O-EX-1-S module
30017 + Offset
Modbus Error Counter for this WI-I/O-EX-1-S module
30018 + Offset
Modbus Last Error Code for this WI-I/O-EX-1-S module. (Section 5.1.3
30019 + Offset
Modbus Lost Link Counter for this WI-I/O-EX-1-S module
30020 + Offset
Module type (0x0301) = 769. / Error Status
40001 + Offset
40008 + Offset
Analog Output 1 8
40009 + Offset
40016 + Offset
Pulsed Output target 1 8 (1 register per pulsed output)
Vista de pagina 115
1 2 ... 111 112 113 114 115 116 117 118 119 120 121 ... 125 126

Comentarios a estos manuales

Sin comentarios