Appendix B: I/O Store Registers
“Output Coils”
0001
0008
Local DIO1 DIO8 as Digital Outputs.
0009
0020
Spare
0021
0500
Space for locally attached WI-I/O-EX-1-S Expansion I/O modules. 20
register per module address, maximum number of modules is 24
(See Appendix C: below for details)
0501
3000
General Purpose Bit Storage Used for:
Staging area for data concentrator
Fieldbus Mappings storage
Force Mapping registers (assigned in Config)
3001
10000
Not Available
“Input Bits”
10001
10008
Local DIO1 DIO8 as Digital Inputs.
10009
10020
Setpoint status from Analog inputs 1 through 12.
10021
10500
Space for locally attached WI-I/O-EX-1-S Expansion I/O modules. 20
register per module address, maximum number of modules is 24
(See Appendix C: below for details)
10501
10595
WIBMesh - General Purpose Bit Storage: Staging area for data
concentrator Fieldbus Mappings storage
WIBNet - Remote Comms Fail Indication corresponds to unit address,
e.g. Remote Address 1 - 95
10596
12500
Continuation of General Purpose Bit Storage: Staging area for data
concentrator Fieldbus Mappings storage
12501
30000
Not Available