1514
3.3 Modules with relay output
SW3=OFF: hysteresis approx. 5% of the set value
SW3=ON: hysteresis app. 10% of the set value
SW4=OFF: relay switches when input > threshold value
SW4=ON: relay switches when input < threshold value
Signal Range SW1 SW2 SW3 SW4
Input 1 Aac OFF ON
5 Aac ON OFF
10 Aac OFF OFF
Signal Range SW1 SW2 SW3 SW4
Input 20 Aac OFF OFF
40 Aac ON OFF
60 Aac ON ON
3.4 Modules with analog outputs
Signal Range SW1 SW2 SW3 SW4 SW5
Input 20/40 Auc OFF OFF
5/25/50 Auc OFF ON
10/30/60 Auc ON OFF
AC Current ON
DC Current OFF
Output 0...10 V ON OFF
0...20 mA OFF OFF
4...20 mA OFF ON
Best.-Nr.
8516560000
8516570000
Best.-Nr.
8513340000
8526600000
Best.-Nr.
8513330000
8526590000
8526610000
8526620000
8545830000
8545840000
Cat. No.
8516560000
8516570000
Cat. No.
8513340000
8526600000
Cat. No.
8513330000
8526590000
8526610000
8526620000
8545830000
8545840000
Signal Range SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
Input 1 Aac OFF OFF ON
5 Aac OFF ON OFF
10 Aac ON OFF OFF
Output 0...10 V ON OFF ON ON OFF
0...20 mA OFF OFF OFF OFF ON
4...20 mA OFF ON OFF OFF ON
Signal Range SW1 SW2 SW3 SW4
Input 1 Aac OFF OFF ON
5 Aac OFF ON OFF
10 Aac ON OFF OFF
Frequenz 50 Hz OFF
60 Hz ON
Signal Range SW1 SW2 SW3 SW4 SW5
Input 5 Aac OFF ON
10 Aac ON OFF
AC Current ON
DC Current OFF
Output 0...10 V ON OFF
0...20 mA OFF OFF
4...20 mA OFF ON
Cat. No.
8523400000
8523410000
Cat. No.
8528650000
8528660000
Cat. No.
8526610000
8526620000