• Setup Sequence
Setting Display Description
Å ì
ENT
S/W Version
v1.21
S/W Version 1.21 (Note: this information only applies to versions
1.20 to 1.29)
Display and Inputs
Input type
IP=1
IP=E
Current (mA)
Voltage (V)
Toggle Accept
Input range
InL=
4.00
Input range lower limit
e.g., 4.00 mA
-
Dec
-
Inc
Next
Accept
InH=
20.00
Input range upper limit
e.g., 20.00 mA
-
Dec
-
Inc
Next
Accept
Input
Calibration?
CIPn
CIPy
Skip input calibration
Calibrate the inputs
Toggle Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Display range
dP=
.
Decimal point position
-
Shift
Next
Accept
dLO=
0.0
Display range lower limit
e.g., 0.0
-
Dec
-
Inc
Next
Accept
dHI=
100.0
Display range Upper limit
e.g., 100.0
-
Dec
-
Inc
Next
Accept
Alarm channel one
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle Accept
Alarm Signal
Proc
rocP
rocn
rocb
Process Measurement
Rate of Change Posititive (Rate of Increase)
Rate of Change Negative (Rate of Decrease)
Rate of Change Both (Rate of Change)
Toggle Accept
Alarm type
A1=L
A1=H
A1=d
Low type (active below setpoint)
High type (active above setpoint)
Deviation Alarm
Toggle Accept
Setpoint value
SP1=
50.0
Setpoint value
e.g., 50.0 %
-
Dec
-
Inc
Next
Accept
Deviation value
dv1=
10.0
Introduces deviation value
e.g., 10.0 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
0.1
Deadband value
e.g., 0.1 %
-
Dec
-
Inc
Next
Accept