Weidmuller WI-I/O-EX: Wireless I/O Expansion Modules v1.11 Manual de usuario Pagina 54

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 55
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 53
WI-I/O-EX Serial I/O Module User Manual v1.11
Page 54 February 2010
On-state voltage <2.1VDC
Wetting current 5mA
Max pulse input rate 1kHz
Minimum pulse width 0.5mS
Max pulse input count 4294967295 (32-bit)
Digital outputs
Output voltage range 0-30VDC
Output current max 200mA
Max pulse output rate 100Hz
Max pulse output count 65535
Analog Inputs
Input voltage range 0-12V
Voltage resolution 16 bits
Input current range 0-24mA
Current resolution 16 bits
Input impedance (voltage) 100k
Input impedance (current) 100ohm
Common mode voltage
range
27VDC
Calibrated accuracy 0.10%
Analog Outputs
Output voltage range 0-12V
Voltage resolution 12 bits
Output current range 0-24mA Total output current 160mA
Current resolution 12 bits
Calibrated accuracy 0.10%
Table D-1: WI-I/O-EX Specifications.
WI-I/O-EX-1-S -11 -12 -13
Digital
inputs/outputs
Up to 16 Up to 8 Up to 8
Pulse outputs
8 8 8
Pulse inputs
4 - -
Analog inputs
- 4 floating / 8
commoned
-
Analog outputs
- - 8
Table D-2: WI-I/O-EX module types and I/O.