Weidmuller WI-I/O-EX: Wireless I/O Expansion Modules v1.11 Manual de usuario Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 55
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
WI-I/O-EX Serial I/O Module User Manual v1.11
WI-IO-EX Manual v1.11 Page 27
4.4 WI-I/O-EX-12 configuration
4.4.1 Voltage input
Voltage inputs may be selected in the scales 0 to 5V, 0 to 10V, or 1 to 5V. For each scale,
the minimum to maximum signal levels are represented by 4000 hex to C000 hex. Table
4-1 shows how the WI-I/O-EX-12 voltage readings translate to outputs in other wireless
products.
WI-I/O-EX-
12 Voltage
scale
WI-I/O-EX-
12
Input voltage
(V)
WI-GTWY
Register value
(hex)
WI-I/O 9-1
Output current
(mA)
WI-I/O 9-3
Output current
(mA)
0 4000 4 4 0 to 5V
5 C000 20 20
0 4000 4 4 0 to 10V
10 C000 20 20
0 2000 0.5
*
0
1 4000 4 4
1 to 5V
5 C000 20 20
Table 4-1: Compatibility of WI-I/O-EX-12 voltage inputs with other products.
*
Reduced accuracy for less than 4mA in WI-I/O-9-1.