WI-I/O-EX Serial I/O Module User Manual v1.11
Page 24 February 2010
Set the “Port” setting to match the computer com port you have connected to.
Set the “Slave Address” to match the address switch setting of the WI-I/O-EX. If you
are using address “00” for E-Series Protocol, set the Slave Address to 100.
Set the communications parameters. The default communications parameters are:
Baud rate: 9600
Parity: NONE
Stop bits: 1
Click the button labeled Connect to WI-I/O-EX.
If you are unable to communicate with the WI-I/O-EX, refer to Appendix C: Comms
Recovery.
If connection has been successful, several folder tabs will become available, depending
on the module type. The panel on the right-hand side of the form shows the WI-I/O-EX
detected and its settings.
4.2 Configuration common to all modules
4.2.1 Communications
Select the Comms folder tab. This page allows you to change the communications
settings of the WI-I/O-EX.
These settings are applied to both the RS-232 configuration port and to the RS-485
ModBus interface port.
Choose the required settings, then click Set comms. You will need to power off / on the
WI-I/O-EX for the new settings to take effect.
Figure 4-2: Communications configuration screen.