20
Wireless I/O
Unidirectional Transmitter/Receiver Units — Introduction
Digital / Pulse Inputs
• Twoinputs,suitableforvoltage-freecontacts/NPN,
orvoltageinput0-1VDCon/>3VDCoffpulseinput
max.rate10Hz,50msecontime.Pulsecountedas1
6-bitregister.
Analog Inputs
• 0-20mA(4-20mA,0-10mA)
• “Floating”differentialinput,resolution16-bit,
accuracy<0.1%
Thermocouple Inputs
• Millivolt(-10mVto+100mV),J,K,orTtype
linearization
withon-boardcold-junctioncompensation
• Accuracybetterthan1°C
Power Supply
• Normal Supply: 9-30VDC,powerconsumption
@12VDC-receivernormal70mA,max.250mA
• Transmitternormal70mA,transmittingmax.600mA
• Analogloopsupplyinternallygenerated,24VDC35mA
• Internalmonitoringofsupplyvoltagemaybe
transmitted
asan“input”(transmitterunitonly)
Set-pointStatus
• Highandlowset-pointsgenerateinternaldigitalstatus-
set-pointstatussets(on)whenanalogvalue<lowset-
pointandresets(off)whenanalogvalue>highset-point.
Statusistransmittedasperdigitalinput,set-pointvalues
aresetviathefrontpanelrotaryswitchorconfiguration
software.
• Separateset-pointsfor(4-20mA),thermocoupleand
supplyinputsareconfigurable
Receiver Outputs
Digital Outputs
• Threerelaycontactoutputs,260V1A
Analog Outputs
• 0-20mA,sourceoutput,12-bitresolution,
0.1%accuracy
Communication Failure
• Internalstatusbasedonconfigurabletime-outvalue
• “Comms-fail”statuscanbeconfiguredtoalocaloutput
Fail-Safe
• On“comms-fail,”outputsuser-configurableasretained
lastcorrectvalueorreset(fail-safe)
Serial Port
• RS232RJ45femaleDCE,usedforconfiguration
anddiagnostics
LED Indication
Transmitter Unit
• Power/OK,radioTX,DIN1,DIN2,analog
set-pointstatus
Receiver Unit
• Power/OK,radioRX,DO1,DO2,DO3,
communicationsfail
• LEDsalsousedtoprovideradiosignalstrength
indication
Configuration and Diagnostics
• Factoryconfigurationtransmitter/receivermatched
pair,AItoAO,2DIto2DO,SPstatustoDO3via
RS232-RJ45cable
• Userconfigurationviaserialport.Unidirectionalunits
canbeconfiguredtonetworkwithmulti-I/Oand
gatewayunits.
• Diagnosticsfeatures:readinputvalues,writeoutput
values,radiosignalstrength,monitorcommunication
messages