DPA/POT 61001038/00/04.08
Bedienungsanleitung
Zweikanaliges
Grenzwertüberwachungsmodul 3
Operating instructions
Two-channel
threshold monitoring module 14
Vista de pagina 0
1 2 3 4 5 6 ... 23 24

Indice de contenidos

Pagina 1 - Operating instructions

deenDPA/POT 61001038/00/04.08BedienungsanleitungZweikanaliges Grenzwertüberwachungsmodul 3Operating instructionsTwo-channel threshold monitoring m

Pagina 2

104. Drehen Sie den Regler SET langsam im Uhrzeigersinn, bis die LED aufleuchtet.Totbandeinstellung (Regler DB)Der Totbandregler dient zum Einstellen

Pagina 3

11• ModifizierungLinke Seitenwand entfernen1. Lösen Sie die sechs mit A-F markierten Schneidklemmschrauben (zuvor Spannungsversorgung abschalten).2.

Pagina 4 - • Betrieb

12(Entsprechend der Schrauben G & H an der linken Seite). Merken Sie sich die Lage des Isoliermaterials.Der Zusammenbau erfolgt in umgekehrter Rei

Pagina 5

13DPA-Hauptplatine und Darstellung der Steckbrücken für Relaisspulenerregung und AlarmfunktionenBrücken für die Auswahl der Relaisspulenerregung:Kanal

Pagina 6

14en DPA/POTContentsOperation 15Installation 16Calibration and Setup 19Modifications 21

Pagina 7

15en DPA/POT• OperationGeneralThe DPA/POT allows you to set two independent trip points on a slidewire/potentiometer wiper position measurement. The a

Pagina 8 - Anschlüsse

16IndicationThe front panel status LEDs indicate an alarm condition regardless of the coil energisation setting.IsolationInput, Power Supply, Alarm Ch

Pagina 9

17Alarm connectionsThe DPA has a high inbuilt immunity to noise spikes caused by switching inductive loads like solenoids or relay coils. However, it

Pagina 10

18Input Signal CablingUse suitable twisted pair cable for the input signal connection.ConnectionsTerminal Signal1 Not usedInput signals2 Wiper3 B (100

Pagina 11 - • Modifizierung

19• Calibration and SetupGeneralThe SET (setpoint) and DB (deadband) adjustments control the setpoint and hysteresis for each alarm channel. Internal

Pagina 13

20Deadband (DB Control) adjustmentThe deadband control adjusts the point at which a tripped alarm resets. This point will be above the setpoint for a

Pagina 14

21• ModificationsRemoving the left hand side plate1. Remove the six self tapping screws marked A-F (disconnect power first).2. Remove the two counter

Pagina 15 - • Operation

22DPA main board showing the locations of the high/low ope ration, andrelay coil energisat ion, selection jumpersRelay energisation selection jumpers:

Pagina 17

Weidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldTel. +49 5231 14-0Fax +49 5231 14-20 83info@weidmuell

Pagina 18 - Connections

3de DPA/POTInhaltsverzeichnisBetrieb 4Installation 5Kalibrierung und Konfiguration 9Modifizierung 11

Pagina 19 - • Calibration and Setup

4de DPA/POT• BetriebAllgemeinDas DPA/POT bietet die Möglichkeit, der Ermittlung von Schleifdraht- und Potentiometerstellungen über zwei unabhängige Sc

Pagina 20

5LED-AnzeigeDie Status-LEDs an der Frontplatte zeigen unabhängig von der Einstellung der Spulenerregung die Alarmzustände an.IsolierungEingangskreis,

Pagina 21 - • Modifications

6AlarmanschlüsseDas DPA zeichnet sich durch eine hohe Störfestigkeit gegenüber Impulsen aus, die beim Schalten induktiver Lasten wie Solenoid- oder Re

Pagina 22

7Verwenden Sie eine für Temperaturen von über 70 °C zugelassene Anschlussleitung (12-28 AWG), und schließen Sie diese mit einem Drehmoment von 0,5 Nm

Pagina 23

8AnschlüsseKlemme Signal1 Nicht belegtEingangssignale2 Schleifer3 B (Stellung 100 %)4 A (Stellung 0 %)5Nicht belegt6789 Neutral (−)Stromversorgung10 P

Pagina 24

9• Kalibrierung und KonfigurationAllgemeinSollwert und Hysterese der einzelnen Alarmkanäle werden über die Potentiometer SET (Sollwert) und DB (Totband